MIL-R-39016/40G
REQUIREMENTS: CONTACT DATA:
Load ratings:
High level (relay case grounded):
Resistive: 2 amperes at 28 V dc maximum; 0.3 ampere at 115 V ac, (60 and 400 Hz). 400 Hz life test not required for qualification testing.
Inductive: 0.75 ampere maximum at 28 V dc maximum with 200 millihenries minimum. Lamp: 0.200 ampere at 28 V dc.
Low level: 10 to 50 ยตA at 10 to 50 mV dc or peak ac. Intermediate current: Applicable.
Contact resistance or voltage drop: Initial: 0.050 ohm maximum.
High level:
During life: Not more than 5 percent of open circuit voltage. After life: 0.100 ohm maximum.
Low level:
During life: 50 ohms maximum. After life: 0.150 ohm maximum.
Intermediate current:
During intermediate current: 3 ohms maximum. After intermediate current: .100 ohm maximum.
Overload (high level only):
Resistive: Two times rated current. COIL DATA: (See table I).
Operate time: 7 ms maximum, inclusive of bounce, over temperature range with rated coil voltage.
Release time: 7 ms maximum, inclusive of bounce, over temperature range from rated coil voltage.