MIL-PRF-28776F
4.8.15 Resistance to soldering heat (see 3.20). Relays shall be tested in accordance with method 210 of MIL-
STD-202. The following details and exceptions shall apply:
a. Depth of immersion in molten solder: Within .060 ±.020 inch (1.52 ±0.51 mm) of the relay base.
b. Test condition: B.
c.
Measurements after test: Insulation resistance, contact resistance (or contact voltage drop), pickup, hold,
dropout, turn-on, and turn-off voltage, and coil current shall be measured as specified in 4.8.5, 4.8.7.1,
d. Examination after test: As specified in 4.8.9e.
4.8.16 Salt spray or salt atmosphere (corrosion) (see 3.21). Relays shall be tested as specified in 4.8.16.1 or,
4.8.16.1 Salt spray, MIL-STD-202 (see 3.21). Unless otherwise specified, relays shall be tested in accordance
with method 101 of MIL-STD-202. The following details and exceptions shall apply:
a.
Applicable salt solution: 5 percent.
b.
Test condition: B.
c.
Examination after test: Relays shall be examined for evidence of peeling, chipping, blistering of the finish,
and exposure of base metal due to corrosion that can adversely affect the operation or performance of the
relay.
4.8.16.2 Salt atmosphere (corrosion), MIL-STD-750-1 (when specified, see 3.1). Relays shall be tested in
accordance with method 1041 of MIL-STD-750-1. The following detail shall apply: Examination after test: As
specified in 4.8.16.1c.
4.8.17 Overload (applicable to high level relays only) (see 3.22). Relay contacts (both normally open and normally
closed) shall be subjected to the tests specified in 4.8.17.1 through 4.8.17.2, as applicable. For double-throw relays,
separate tests shall be performed for the normally open and the normally closed contacts. Relay coil energization
shall be nonsynchronous with the power supply for ac loads. The number of cycles shall be 100 for dc contact loads,
and 200 for ac contact loads ("on" and "off" times shall be approximately equal). The coil circuit shall be energized at
rated voltage. Overload current shall be twice the rated load current. The opening and closing of all contacts under
test shall be continuously monitored to detect switching of the contacts. The equipment shall be capable of
monitoring 40 percent minimum of the actual opened and closed time of each contact. The equipment shall
automatically cut off when a failure occurs, or shall record any failures. The relay case shall be connected to system-
ground through a normal-blow fuse rated at 5 percent of the test current or 100 mA, whichever is greater. After the
test, the fuse shall be tested for electrical continuity.
4.8.17.1 Resistive load. Suitable noninductive resistors shall be used. Cycling rate shall be 20 ±2 cycles per
minute (cpm).
4.8.17.2 Inductive load. Cycling rate shall be 10 ±1 cpm. Inductive load testing should be performed as
recommended by MIL-HDBK-338 and approved by the qualifying activity.
37
For Parts Inquires call Parts Hangar, Inc (727) 493-0744
© Copyright 2015 Integrated Publishing, Inc.
A Service Disabled Veteran Owned Small Business