MIL-PRF-28776F
4.8.13 Magnetic interference (when specified, see 3.1 and 3.18). The relay under test and eight similar relays
shall be mounted in the same physical orientation by nonmagnetic means, as shown on figure 8. Unless otherwise
specified, grid-spaced relays shall be mounted so that all terminals are positioned in the closest possible grid pattern.
Unless otherwise specified, the spacing between terminals and tops of adjacent terminals shall be as shown on figure
8. Pickup, hold, dropout, turn-on, and turn-off voltages shall be measured on the relay under test as specified in
4.8.7.2, 4.8.7.4, and 4.8.7.5 with the coils of the eight outer relays energized at rated voltage (the magnetic polarity of
each relay shall be similarly oriented). This measurement shall be repeated with the coils of the eight outer relays de-
energized.
4.8.14 Coil life (unless otherwise specified, see 3.1) (see 3.19). Relays shall be tested for 1,000 hours as follows
(see figure 9).
Relays may be mounted as specified in 4.3.6. Each contact terminal shall be connected as specified in
a.
During the maximum temperature portion of the test, rated coil supply voltage (see 3.1) shall be applied
b.
continuously and at least half of the normally open contacts shall carry rated current. During room
temperature and minimum temperature exposures, the coil circuit shall be de-energized and contacts shall
not be loaded. Ambient temperatures shall be varied as shown on figure 9, with heating and cooling rates
not to exceed +1°C per second average. The portion of the cycle run at minimum temperature shall be
approximately 10 percent of the test cycle time.
c.
After the first 100 hours, and while still at the low temperature extreme, contact resistance (or voltage drop)
and turn-on and turn-off time shall be measured as specified in 4.8.7.1 and 4.8.7.6 and the values shall be
recorded. Measurements of coil current as specified, and contact resistance as specified in 4.8.7.3 and
4.8.7.1, shall be taken at room temperature initially, then again after 250 ±25, 500 ±25, and 750 ±25 hours
and the values shall be recorded. Pickup, hold, dropout, turn-on voltage or current, and turn-off voltage
measurements shall be made as specified in 4.8.7.2, 4.8.7.4, and 4.8.7.6, respectively during the last
temperature cycle after allowing the relay to stabilize, deenergized at each of the temperature extremes,
and the values shall be recorded.
d.
After the relay(s) have been subjected to the coil life temperature cycles, measurements shall then be taken
at room temperature of dielectric withstanding voltage, insulation resistance, contact resistance (or contact
voltage drop), coil current, turn-on and turn-off time, and contact bounce as specified in 4.8.6.1, 4.8.5,
4.8.7.1, 4.8.7.3, 4.8.7.6, and 4.8.7.7, respectively. Relays shall then be examined for evidence of damage.
e.
Following the test, the coil current or resistance, as applicable, shall be measured in accordance with 3.12.3
and shall be as specified (see 3.1).
35
For Parts Inquires call Parts Hangar, Inc (727) 493-0744
© Copyright 2015 Integrated Publishing, Inc.
A Service Disabled Veteran Owned Small Business