MIL-PRF-28750F
Apply specified (see 3.1) input conditions, and activate the necessary status conditions to turn the status
c.
output ON.
Verify that the status turn-on time is as specified (see 3.1).
d.
4.7.7.8 Status "ON" voltage (see 3.13.14).
a.
Test setup in accordance with figure 1.
Apply specified (see 3.1) load, voltage, and frequency (if applicable).
b.
c.
Apply specified (see 3.1) input conditions, and activate the necessary status conditions to turn the status
output ON.
Verify that the status current I(status) is as specified (see 3.1) and that the status "ON" voltage Vs(on) is as
d.
specified (see 3.1).
4.7.7.9 Status turn-off time (see 3.13.15).
a.
Test setup in accordance with figure 1.
Apply specified (see 3.1) load, voltage, and frequency (if applicable).
b.
c.
Apply specified (see 3.1) input conditions, and activate the necessary status conditions to turn the status
output OFF.
Verify that the status turn-off time is as specified (see 3.1).
d.
4.7.7.10 Status "OFF" voltage (see 3.13.16).
a.
Test setup in accordance with figure 1.
Apply specified (see 3.1) load, voltage, and frequency (if applicable).
b.
c.
Apply specified (see 3.1) input conditions, and activate the necessary status conditions to turn the status
output OFF.
Verify that the status current I(status) is as specified (see 3.1) and that the status "OFF" voltage Vs(off) is as
d.
specified (see 3.1).
4.7.7.11 Status blocking voltage (see 3.13.17).
a.
Test setup in accordance with figure 1.
Apply specified (see 3.1) load, voltage, and frequency (if applicable).
b.
c.
Apply specified (see 3.1) input conditions and necessary status turn off conditions.
Apply the specified (see 3.1) status blocking voltage, V(status).
d.
26