MS24152J
REQUIREMENTS:
Dimensions and configuration: See figure 1.
Dash number and general characteristics: See table I.
TABLE I. Dash number and general characteristics.
PIN MS24152- |
Type |
Coil type |
Terminal type |
Mounting or mating socket |
Auxiliary terminals |
Max weight (pounds) |
D1 |
II |
dc |
Stud |
Flange |
None |
2.3 |
Contact data:
Load ratings: See table II.
Maximum contact drop, initial: 0.150 V. After life test: 0.175 V.
Overload current (NO): 200 amperes. Rupture current (NO): 250 amperes.
TABLE II. Rated contact load (amperes per pole) (case grounded). 1/
Type of load |
Life oper- ating cycles x 103 |
28 V dc |
115 V ac, 1 phase |
115/200 V ac, 3 phase 2/ |
|||||||||
Main |
Aux |
Main |
Aux |
Main |
Aux |
||||||||
NO |
NC |
NO |
NC |
400 Hz |
60 Hz |
400 Hz |
60 Hz |
400 Hz |
60 Hz |
400 Hz |
60 Hz |
||
Resistive |
50 |
25 |
25 |
25 |
|||||||||
Inductive |
10 |
25 |
25 |
25 |
|||||||||
Motor |
50 |
25 |
25 |
25 |
|||||||||
Lamp |
|||||||||||||
Transfer load 3/ |
|||||||||||||
Mechanical life reduced current |
100 |
6.3 |
6.3 |
6.3 |
|||||||||
Mixed loads |
50 |
2.5 |
2.5 |
2.5 |
1/ Absence of value indicates parameter is not applicable to this specification.
2/ Absence of value indicates relay is not rated for three phase applications.
3/ Transfer load indicates relay is suitable for transfer between unsynchronized ac power supplies at rating indicated.
3
For Parts Inquires call Parts Hangar, Inc (727) 493-0744
© Copyright 2015 Integrated Publishing, Inc.
A Service Disabled Veteran Owned Small Business