MIL-PRF-28776F
4.8.10.2 Vibration (random). Relays shall be tested in accordance with method 214 of MIL-STD-202. The
following details and exceptions shall apply:
Method of mounting: As specified in 4.8.9a.
a.
b.
Electrical-load conditions: For qualification and group C inspections, relays shall be tested with the relay
energized at rated voltage for 15 minutes and with the coil de-energized for 15 minutes, in each of three
mutually perpendicular (x, y, and z) directions. When applicable to group A inspection, the test time shall
be 3 minutes for each state described above. Contacts shall monitored as specified in 4.8.10.2d.
Test condition: G (0.4 G2/Hz, 23.91 rms G).
c.
d.
Tests during vibration: As specified in 4.8.9d.
e.
Examination after test: As specified in 4.8.10.1f.
4.8.11 Acceleration (unless otherwise specified, see 3.1 and 3.16). Relays shall be tested in accordance with
method 212 of MIL-STD-202. The following details and exceptions shall apply:
a.
Mounting of specimens: As specified in 4.8.9a.
b.
Test conditions: Unless otherwise specified (see 3.1), test condition A, 50 G's, (acceleration shall be
applied in each direction along three mutually perpendicular axes (x, y, and z) of the specimen; one axis
shall be in the direction most likely to cause malfunction). In each direction, the coil shall be de-energized
for 5 minutes, rated coil voltage shall be momentarily applied, and the voltage shall be reduced to the
maximum ambient pickup voltage as specified (see 3.1) for 5 minutes. Contacts shall be monitored for
proper position.
c.
Examination after test: As specified in 4.8.9e.
4.8.12 Terminal strength (see 3.17). Relays shall be tested in accordance with method 211 of MIL-STD-202 in
accordance with the following, as applicable. Unless otherwise specified herein, two terminals of each discrete
design, size, and configuration shall be tested; however, if there be only one of such design, size, and configuration, it
shall be tested.
4.8.12.1 Pull test (all terminal types). Terminals shall be tested as specified in test condition A; the force shall be
as specified (see 3.1).
4.8.12.2 Bend test (all terminal types). Terminals shall be tested as specified in test condition B (two bends) or C,
as applicable. Loads for test condition C shall be as specified (see 3.1).
4.8.12.3 Twist test (wire lead terminals only) (not applicable to relays with spreader mounting pads or leads less
than .50 inch (12.7 mm) in length). All terminals shall be tested as specified in test condition D, except during
application of torsion, each terminal shall be rotated 45° in one direction, then returned to start; rotated in opposite
direction 45°, then returned to start. Each terminal shall be subjected to two such rotations and returns. Each
terminal shall be held at a point .75 inch (19.05 mm) from the point of emergence from the relay, or terminal end for
relays with terminals less than .75 inch (19.05 mm), and in one plane shall be bent 20° ±5° in one direction, then
returned to start; bent in opposite direction 20°±5°, then returned to start. This procedure shall then be repeated in
the perpendicular plane. Following these tests, relays shall be examined for evidence of loosening or breaking of the
terminals and other damage that could adversely affect the normal operation of the relay; the requirements of 3.29
are not applicable.
34
For Parts Inquires call Parts Hangar, Inc (727) 493-0744
© Copyright 2015 Integrated Publishing, Inc.
A Service Disabled Veteran Owned Small Business