MIL-PRF-28776F
4.8.2 Screening (see 3.7).
4.8.2.1 Internal moisture. Relays (coil de-energized) shall be held at +15°C to +25°C for a minimum of 30 minutes.
The insulation resistance of all contact pins to case only shall be measured and observed. The relay coil shall be
energized with 140 percent of rated voltage for a period of 2 minutes 30 seconds. 3/ The insulation resistance of all
contact pins to case only shall be verified a minimum of once each 30 seconds during this period and the lowest
value shall meet the requirements of 3.7.
4.8.2.2 Run-in.
a.
High temperature. For qualification inspection only; relays shall be subjected to +125°C with rated supply
voltage on the coil for 1 hour. For group A testing, relays shall be subjected to +125°C; the test chamber
shall stabilize at +125°C after the specimens have been inserted into the test chamber. The test shall be
performed with rated supply voltage on the coil circuit for 15 minutes minimum for relays weighing 1 ounce
or less and 30 minutes minimum for relays weighing over 1 ounce but not more than .3 pound. The
specified pickup value (voltage) shall be measured to determine compliance with 3.1. While at this
temperature, the relays shall be subjected to a 2,500 cycle run-in test. The cycling rate shall be calculated
using the formulas below and the maximum turn-on and turn-off times as specified, see 3.1 for the relay
under test. Relays shall have the contacts loaded as follows: Open circuit load voltage 10 to 50 mV dc or
peak ac. The load current shall be 10 to 50 µA. The contact resistance or voltage drop, as applicable, of
each pair of mated contacts shall be monitored during 40 percent minimum of each "on" and each "off"
period. The monitoring equipment shall automatically turn off when a failure occurs, or shall record every
failure.
b.
Low temperature. Following high temperature, for qualification only, relays shall be subjected to -65°C with
the coil or coils de-energized for 1 hour. For group A testing, relays shall be subjected to -65°C; the test
chamber shall stabilize at -65°C after the specimens have been inserted into the test chamber. The test
shall be performed with the coil de-energized for 15 minutes minimum for relays weighing 1 ounce or less
and 30 minutes minimum for relays weighing over 1 ounce but not more than .3 pound. At the end of either
period, the specified dropout value (voltage) shall be measured to determine compliance with 3.1. While at
this temperature, the relays shall be subjected to a 2,500 cycle run-in test in accordance with the procedure
outlined in 4.8.2.2a.
0.1
Maximum cycle rate
Maximum turn on time Maximum turn off time
(cycles per sec ond )
(sec onds)
(sec onds)
4.8.3 Solderability (see 3.8). Relays shall be tested in accordance with method 208 of MIL-STD-202. The
following detail and exception shall apply: All terminations of each part shall be tested.
4.8.4 Seal (see 3.9). Relays shall be tested in accordance with 4.8.4.1 as applicable. In case of dispute, method
1014 of MIL-STD-883, test condition B shall govern.
______________
3/ Wherever "coil shall be energized" is used herein, it is considered to include turn-on voltage applied.
24
For Parts Inquires call Parts Hangar, Inc (727) 493-0744
© Copyright 2015 Integrated Publishing, Inc.
A Service Disabled Veteran Owned Small Business