MIL-R-5757/10L
LIFE TEST REQUIREMENTS:
High level: 100,000 operations per relay.
Two relays per contact rating shall be tested with rated loads on all contacts, except minimum current.
For qualification inspection, the resistive and inductive 28 V dc loads and the resistive, inductive, and lamp 115 V,
60 Hz loads shall be used when performing the high-level life test. Low level: 100,000 operations per relay.
Intermediate current: 50,000 operations.
VERIFICATION: Group A.
Group A1: Run-in (high level) test load 100 mA at 28 V dc utilizing 10 percent of line drop; (low level) test load
10 mA maximum at 30 mV dc maximum. QUALIFICATION: See tables III and IV.
TABLE III. Qualification inspection and sample size.
Single submission |
Group submission |
|
High level: with minimum current 22 units plus 1 open unit. Qualification inspection as applicable. |
M5757/10-039 M5757/10-036 M5757/10-056 |
20 units plus 1 open unit. Qualification inspection as applicable. 2 units each part number. Shock, vibration, terminal strength, and qualification inspection, Q1. |
Low level: 12 units plus 1 open unit. Qualification inspection as applicable. |
M5757/10-022 |
2 units. Qualification inspection, Q1 plus life and seal. |
9