MIL-DTL-26126C
lead finish is acceptable, provided that lead content is at least 3 percent. Zinc plating and cadmium
plating are prohibited internally and externally.
3.5 Performance.
3.5.1 Dielectric withstanding voltage. When tested as specified in 4.6.2, relays shall withstand the test
voltage specified without damage, and there shall be no leakage current in excess of 1.0 milliampere (mA)
nor evidence of damage due to arcing (air discharge), flashover (surface discharge), or insulation
breakdown (puncture discharge).
3.5.2 Calibration.
3.5.2.1 Pickup voltage. When relays are tested as specified in 4.6.3.1, the pickup voltage shall be
within the specified voltage limits (see 3.1).
3.5.2.2 Time-voltage characteristics. When tested as specified in 4.6.3.2, the time voltage
characteristics shall be within the limits of figure 1 at each of the specified voltages.
3.5.3 Endurance. Relays shall be cycled with contacts loaded in accordance with 4.6.4. After the
tests, the fuse shall be tested for continuity. A blown fuse is considered a relay failure. After the test, the
relay shall meet the calibration requirements specified in 3.5.2.
3.5.4 Overload. When relays are tested as specified in 4.6.5, they shall not be damaged. After the
test, the relays shall meet the pickup voltage requirements specified in 3.5.2.1. The input voltage drop
shall not exceed 7 percent during the load period.
3.5.5 High temperature. When tested as specified in 4.6.6, the relays shall meet the calibration
requirements specified in 3.5.2. During high temperature testing, no solder joint connected to a resistor
within the relay shall attain a temperature within 75°C of the softening temperature of solder.
3.5.6 Low temperature. When tested as specified in 4.6.7, the relays shall meet the requirements of
4.6.3.
3.5.7 Vibration.
3.5.7.1 Vibration (endurance). When tested as specified in 4.6.8.1, with the relay sensing circuit
energized with 29 V dc, the contacts shall not close for more than 10 microseconds. When tested with the
relay sensing circuit de-energized, the relay contacts shall not close for more than 10 microseconds.
There shall be no damage to or malfunction of the relay during the test. Following this test, the relay shall
meet the calibration requirements specified in 3.5.2.
3.5.7.2 Vibration (calibration). When tested as specified in 4.6.8.2, the relay shall meet the
requirements of figure 2. Following the test, the relay shall meet the pickup voltage requirements
specified in 3.5.2.1.
3.5.8 Low-temperature altitude. When tested as specified in 4.6.9 (see figure 2), immediately after the
2-minute coil energization, the relay shall meet the calibration requirements specified in 3.5.2.
4
For Parts Inquires call Parts Hangar, Inc (727) 493-0744
© Copyright 2015 Integrated Publishing, Inc.
A Service Disabled Veteran Owned Small Business